Chapter 7: Service and troubleshooting
EST3X Technical Reference Manual 185
Pseudo points
A pseudo point is an input or output point that is not a physical device. For
example, ground fault and communication fault notifications. When a pseudo
point event occurs, a message displays on the control panel LCD screen that
shows the point address and label. You can find the pseudo point source and
description by cross-referencing to the pseudo point Address column in the
tables that follow.
Table 50: System pseudo points
Address
Label Source Description
0001
Startup Response CPU The system c
hanges to the active state when
the panel is energized or when an operator
initiates a restart from the LCD command
menu
0002
First Alarm Response CPU The system changes to the active state when
the first point on a panel or any panel in the
same network routing group changes to the
alarm state
0003
First Supervisory
Response
CPU The system changes to the active state when
the first point on a panel or any panel in the
same network routing group changes to the
supervisory state
0004
First Trouble Response CPU The system changes to the act
ive state when
the first point on a panel or any panel in the
same network routing group changes to the
trouble state
0005
First Monitor Response CPU The system changes to the active state when
the first point on a panel or any panel in the
same network routing group changes to the
monitor state
0006
Evacuation Response CPU The system changes to the active state when
an operator presses a switch that executes
the Evacuation command
0007
Drill Response CPU The system changes to the active state when
an operator presses a switch that executes
the Drill command
0008
AllCall Response CPU The system changes to the active state when
an operator presses the All Call or All Call
Minus switch on the 3X-PMI
0009
Alarm Silence Response CPU The system changes to the active state when
an operator presses a switch that executes
the Alarm Silence command