Chapter 7: Service and troubleshooting
178 EST3X Technical Reference Manual
Possible cause
LEDs respond incorrectly • The control-display is not defined in the 3-SDU
• The control-display LED is not identified in the 3-SDU
• A rule governing LED operation is not correctly written
utton does not perform the
• The control-display is not defined in the 3-SDU
• The button is not identified correctly in the 3-SDU
• A rule governing button operation is not correctly written
3-ZAxx zoned amplifier modules troubleshooting
Table 44: 3-ZAxx Zoned Audio Amplifier module troubleshooting
Possible cause
udio output level is too
• A jumper is set for 25 VRMS but connection is to
circuit
• The gain is set too low
• The auxiliary input level to the 3X-PMI is too low
o audio output or is
• An open fuse needs replaced (not field replaceable)
• The gain is set too low
• The prerecorded message/tone is too low
• There is an incorrect channel activation
udio output level is too
• A jumper is set for 70 VRMS but connection is to a
circuit
• The gain is set too high
• The input level to the 3X-PMI is too high
mplifier current is limiting • The audio circuit overloaded
• The input level to the 3X-PMI is too high
ncorrect amplifier version
reported by the CPU
• The jumpers are installed incorrectly
• An incorrect model amplifier installed