EasyManua.ls Logo

EST EST3X - 3-Zaxx Zoned Amplifier Modules Troubleshooting

EST EST3X
298 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7: Service and troubleshooting
178 EST3X Technical Reference Manual
Problem
Possible cause
The
LEDs respond incorrectly The control-display is not defined in the 3-SDU
The control-display LED is not identified in the 3-SDU
A rule governing LED operation is not correctly written
A b
utton does not perform the
expected function
The control-display is not defined in the 3-SDU
The button is not identified correctly in the 3-SDU
A rule governing button operation is not correctly written
3-ZAxx zoned amplifier modules troubleshooting
Table 44: 3-ZAxx Zoned Audio Amplifier module troubleshooting
Problem
Possible cause
The a
udio output level is too
low
A jumper is set for 25 VRMS but connection is to
a 70 VRMS
circuit
The gain is set too low
The auxiliary input level to the 3X-PMI is too low
There is n
o audio output or is
extremely low
An open fuse needs replaced (not field replaceable)
The gain is set too low
The prerecorded message/tone is too low
There is an incorrect channel activation
The a
udio output level is too
high
A jumper is set for 70 VRMS but connection is to a
25 VRMS
circuit
The gain is set too high
The input level to the 3X-PMI is too high
The a
mplifier current is limiting The audio circuit overloaded
The input level to the 3X-PMI is too high
An i
ncorrect amplifier version
is
reported by the CPU
The jumpers are installed incorrectly
An incorrect model amplifier installed

Table of Contents

Other manuals for EST EST3X

Related product manuals