Chapter 3: Operating instructions
EST3X Technical Reference Manual 59
• Zone group: A collection of input devices that are grouped in the database to
provide a unique response separate from their individual device responses.
Zone groups can be configured to go into alarm when any member of the
group goes active or when any device in the group goes into trouble.
• Instruction text group: A collection of devices that are grouped in the
database to provide additional detailed instructions or warnings when any
device in the group changes to a qualified active state.
To disable a group:
1. Access the Main Menu, and then click Disable.
2. Click Group, and then select the group type.
3. Click the group from the group list.
4. Enter the access level password.
To enable a group:
1. Access the Main Menu, and then click Enable.
2. Click Group, and then select the group type.
3. Click the group from the group list.
4. Enter the access level password.
Disabling and enabling system time controls
System time controls are configured in the 3-SDU to set up automatic starting
and stopping of system events based on time and date. The controls run in the
background and do not require any operator action. In the event you need to
disable a control, you can do so from the control panel.
To disable a time control:
1. Access the Main Menu, and then click Disable.
2. Click Time Control, and then click the desired time control.
3. Enter the access level password.
To enable a time control:
1. Access the Main Menu, and then click Enable.
2. Click Time Control, and then click the desired time control.
3. Enter the access level password.