Chapter 2: Product description
EST3X Technical Reference Manual 27
Access level Description
4 Disables an option card or control-display module; requires the
panel and card address
Level 3: AND,
Matrix, Guard
Patrol, Zone,
and Inst Text
groups
Level 4:
Service Group
Displays the Disable Group Menu from which you can disable
the following:
• AND Group: Select from a list of AND groups
• Matrix Group: Select from a list of Matrix groups
• Service Group: Select from a list of Service groups
• Guard Patrol Group: Select from a list of Guard Patrol
• Zone Group: Select from a list of Zone groups
• Inst Text Group: Select from a list of Instruction Text groups
3 Displays a list of the programmed time controls, from which a
time control may be disabled
3 Disables a switch on a control-display module; requires the
panel, card, and device address
3 Disables the LEDs on a control-display module; requires the
panel, card, and device address
Activate Menu
Use the commands on the Activate Menu to switch outputs and LED indicators
on, and switch sensor sensitivity and event message routing to alternate settings.
Table 13: Activate Menu selection descriptions
Access level Description
None Returns to the previous menu.
None Returns to the event message screen.
2 Switches fire detector sensitivity settings from primary alarm
sensitivity to alternate alarm sensitivity.
2 Switches event message routing from primary message
routing to alternate message routing.
3 Provides a list of guard patrol routes.
3 Activates a relay or output module. Select one of the states
from the Output Priority Menu. Requires a panel, card, and
device address.
• Set: Overrides low, medium, and high priority commands
and forces the device to the desired state. The S
does not reset the device’s priority counters.
• Latch: Overrides low, medium, and high priority
commands and forces the de
vice to the desired state. The
Latch priority does reset the device’s priority counters.