3. From the EST3X control panel, access the Main Menu, and then click
Activate.
4. Click Remote Write Unlock.
5. Click By Panel, and then enter the panel address and access level password.
or
Click All Panels, and then enter the access level password.
6. From the 3-SDU on the connected computer, configure the communication
functions for a TCP/IP connection, and then download the database.
Press F1 to open the 3-SDU Help topics, if necessary.
7. When the download is finished, access the Main Menu, and then click
Restore.
8. Click Remote Write Unlock.
9. Repeat step 3. If the user time out period has expired, reenter the access
level password.
RS-232 download
To download the project database using the RS-232 telephone jack:
1. Connect one end of a standard RS-232 cable to the RJ-11 modular telephone
jack on the SFS1-CPU. See Figure 10 on page 70.
2. Connect the other end of the cable to the RS-232 jack on the computer with
the project database.
3. From the 3-SDU on the connected computer, configure the communication
functions, and then download the database.
Press F1 to open the 3-SDU Help topics, if necessary.
To download the project database using the RS-232 terminal block:
Note: Requires a separately ordered programming cable, P/N 260097.
1. Connect one end of a DB-9 programming cable to the terminal block on the
SFS1-CPU. See Figure 10.
2. Connect the other end of the cable to the RS-232 jack on the computer with
the project database.
3. From the 3-SDU on the connected computer, configure the communication
functions for an RS-232 connection, and then download the database.
Press F1 to open the 3-SDU Help topics, if necessary.