Appendix C: Programming options
274 EST3X Technical Reference Manual
Programming options
For programming instructions, refer to the 3-SDU Help.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION,
AND OTHER INVOLVED PARTIES:
This product incorporates field-programmable software. In order for the product
to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Permitted
in UL 864?
(Y/N)
Possible
settings
Settings
permitted
in UL 864
Telephone line supervision
Y No / Yes Yes
Y No / Yes No [1]
Yes
Y 00:00:00
to 99:59:59
00:00:00 [2]
to 24:00:00
Y Disabled
01:00 to 45:00
01:00 to 03:00
Y All Cabinets
No Cabinets
User defined routes
(1 to 15)
All Cabinets
No Cabinets [3]
User defined routes (1 to
15) [4]
Event message display filtering:
Alarm
, Supervisory, and Trouble
Y Enabled
Disabled
Enabled
Disabled [5]
Delays (programmed in rules)
Y 0 to 65,535 seconds 0 to 65,535 seconds [6]
verification Y 0 to 56 seconds 0 to 44 seconds
event reporting priority
Y 1 to 255 1 to 255 [7]
activate and restore
messages (programmed in rules)
Y Send on activation
Send on restoration
Activation and restoration
triggers must match the
message type
group member device types Y GENALARM
SMOKE
SMOKEVFY
HEAT
PULL
STAGEONE
STAGETWO
WATERFLOW
GENALARM
SMOKE
SMOKEVFY [8]
HEAT
PULL
STAGEONE [8]
STAGETWO [8]
WATERFLOW