Chapter 2: Product description
EST3X Technical Reference Manual 31
Access level Description
3 Restores the output state of an audio amplifier. Select one of
the states from the Output Priority Menu. Requires a panel,
card, and device address.
• Set
• Latch
• Low Priority
• Medium Priority
• High Priority
3 Restores the message and channel for a corresponding
amplifier. Requires the message and channel for a panel,
card, and device address.
None Cancels the drill signal.
2 Returns the panel to the unlocked state by either panel or all
panels.
2 Returns the panel to the locked state by either panel or all
panels.
2 Returns the photo element on a SIGA2-PHS Multisensor
Smoke Detector to normal supervisory messaging. Requires a
panel, card, and device address.
2 Returns the CO rate of detection for a CO detector to normal.
Requires a panel, card, and device address.
Reports Menu
Use the commands on the Reports Menu to retrieve maintenance and service
related information from the control panel. There are four kinds of reports:
Maintenance, History, Revisions, and MODCOM compliance.
Table 15: Reports Menu
Access level Description
None Returns to the previous menu.
None Returns to the event message screen.
nance
None Lets you select one of the reports described below.
• Dirty Devices > 80%: Lists all addressable smoke
detectors that have a %Dirty value of 80% and greater.
Smoke detectors that are more than 80% dirty should be
cleaned or replaced as soon as possible. Requires a
panel address. You can select to display or print the
report.
• Dirty devices > 20%: Lists all addressable smoke
detectors that have a %Dirty value 20% and greater. A