Chapter 2: Product description
32 EST3X Technical Reference Manual
Selection
Access level Description
smoke detector that is more than 20% dirty should be
noted for possible cleaning or replacing.
Requires a panel
address. You can select to display or print the report.
Single Device: Lists the %Dirty value for a single smoke
detector. The report also includes the smoke detector’s
model type, primary and alternate alarm se
nsitivity values,
and, if programmed, a location description. Requires a
panel, card, and device address. You can select to
display or print the report.
Devices on a card: Lists the %Dirty value for all of the
smoke detectors on a signaling line circuit. The report
also includes each smoke detector’s model type, primary
and alternate alarm sensitivity values, and, if
programmed, a location description. Requires a panel,
card, and loop controller address (L). You can select to
display or print the report.
History
None Creates a report that lists the last 1,000 events and operator
commands processed by the control panel. The items in the
list are presented in reverse chronological order. The event or
system command name, address, time and date of
occurrence, and the source that initiated the event or
command are included.
Requires a panel address. You can select to display or print
the report for the following:
History with Text: Provides a history of events and
operator commands logged by the panel. For each point
that activated or restored, the detail includes the point’s
message text.
History without Text: Provides a history of events and
operator commands logged by the system
. For each point
that activated or restored, the detail includes the point’s
device address.
Revisions
None
Creates a report that lists the revision level of all the hardware
and software components installed in the cabinet. Requires a
panel address. You can select to display or print the report.
MODCOM
Compliance
None Creates a report of the installed MODCOM address and its
NFPA compliance. Requires a panel address. You can select
to display or print the report.
Note: If “Fully Programmable” was selected in the 3-SDU for
the MODCOM setting, the panel will report that it is
noncompliant. However, individual rules could have been
written in the 3-SDU that make it compliant.