Chapter 6: Preventive maintenance and testing
156 EST3X Technical Reference Manual
Replacement smoke chambers are listed below.
Model
Replaces smoke chamber on:
2
-SPRC1 SIGA2 -PS, SIGA2-PHS
2
-SPRC2 SIGA2-PCOS, SIGA2-PHCOS
CO sensor module
Signature Series CO detectors use a 2-CORPL replacement sensor. Replace the
sensor every 6 years, or when the control panel indicates a sensor end-of-life
condition. Refer to the 2-CORPL CO Replacement Module Installation Sheet
(P/N 3101589) for instructions.
Note: For proper operation, never replace the CO sensor itself without the PCB
because each board has calibration data specific to the CO sensor.
Maintenance schedule
Table 35: Routine maintenance schedule
Component
Frequency
Control equipment
[1] Quarterly/Annually
Supervisory signal devices (except valve tamper switches)
Quarterly
Off
-premises transmission equipment Quarterly
Waterflow devices
Semiannually
Valve tamper switches
Semiannually
Batteries [2]
Annually
Control unit trouble sig
nals Annually
Fiber optic cable connections
Annually
Emergency voice/alarm communication equipment
Annually
Remote annunciators
Annually
Smoke detectors
Annually
Heat detectors
Annually
Fire alarm boxes
Annually
Fire extinguishing systems or suppres
sion systems Annually
Guard tour equipment
Annually
Interface equipment
Annually
Audible notification appliances
Annually