Chapter 3: Operating instructions
42 EST3X Technical Reference Manual
Monitor state
The control panel enters the monitor state when a supervisory or monitor input is
activated.
Output of the monitor state
Upon entering the monitor state, the control panel:
Activates the first monitor pseudo point
Changes the active state for the point that signaled the monitor event
Indication of the monitor state
To indicate it is in the monitor state, the control panel:
Sounds the panel buzzer
Displays the point’s event message in the Monitor Queue, provided there are
no higher priority events
If the point is a monitor zone and a control-display module is installed, the control
panel also flashes the zone’s active LED on the module.
Note: Monitor indications are restored automatically when the monitor input is
restored.
Test state
The control panel enters the test state when a service group is activated.
Output of the test state
Upon entering the test state, the control panel:
Activates the first monitor pseudo point
Activates the first trouble pseudo point
Activates the first test pseudo point
Changes the active state for the service group that was activated
While in the test state:
When a member of an active service group signals an active event, the
control panel executes the service group’s active test response
When a member of an active service group signals a trouble event, the
control panel executes the service group’s trouble test response
Note: If you do not program a trouble test response, the control panel executes
the active test response instead.