Chapter 2: Product description
EST3X Technical Reference Manual 35
Security Menu
Use the commands on the Security Menu to set the device bypass and monitor
state of a security partition when the EST3X control panel is integrated with an
EST3 life safety network that includes security features.
Note: The Security Menu is only available when the security control function is
enabled in the 3-SDU.
Table 18: Security Menu selection descriptions
Selection
Access level Description
Back
None Returns to the previous menu.
Exit Menu
None Returns to the event message screen.
Device
2 Sets the bypass state of a security alarm in a security
partition. The parti
tion must be disarmed before you can set
the bypass state.
Select either Bypass or Remove Bypass. Requires the
panel, card, and device address.
Partition
2 Sets the monitoring state for a security partition.
Select one of the following:
Partition Disarm: Displays a list of armed partitions that
can be disarmed.
Partition Away: Displays a list of partitions to arm.
“Away” arms the partition so the system monitors all
devices, both perimeter and interior of the protected
area.
Partition Stay: Displays a list of partitions to arm. “Stay”
arms the partition so the system monitors only those
devices on the perimeter of the protected area.
Partition Reset: Displays a list of partitions that can be
reset.