Chapter 3: Operating instructions
EST3X Technical Reference Manual 41
Activates the first supervisory pseudo point
Changes the active state for the point that signaled the supervisory event
Indication of the supervisory state
To indicate it is in the supervisory state, the control panel:
Sounds the panel buzzer
Flashes the SUP LED
Displays an event message in the Supervisory Queue for the point that
signaled the supervisory event, provided there are no higher priority events
If the active point is a supervisory zone and a control-display module is installed,
the control panel also flashes the zone’s active LED on the module.
Trouble state
The control panel enters the trouble state when a point signals a trouble event.
Output of the trouble state
Upon entering the trouble state, the control panel:
Activates the common trouble contacts on the main board
Activates the first trouble pseudo point
Changes the active state for the point that signaled the trouble event
Indication of the trouble state
To indicate it is in the trouble state, the control panel:
Sounds the panel buzzer
Flashes the Trouble LED
Turns on the GND Fault LED if the trouble is an earth ground fault
If the point is an alarm, supervisory, or monitor zone and a control-display
module is installed, the control panel also flashes the zone’s Trouble LED on the
module.