Chapter 5: Installation
108 EST3X Technical Reference Manual
Figure 24 on page 109 shows an auxiliary/booster power supply being used to
power the NAC, to provide synchronization and horn silence capability. Because
the auxiliary/booster supply has the ability to silence the horn circuit, this
application can be created using only the Signature loop wiring.
The SIGA-CT1 module monitors the power supply for AC failure. The SIGA-CR
module signals the power supply to turn the horns on or off. The SIGA-CC1
module signals the power supply when the system goes into alarm, turning the
NAC on.
Notes
The power supply can only synchronize the notification appliances to which it
is connected. If you need to synchronize several similar NACs on the same
Signature loop, you can use a SIGA-CC1S module in place of the SIGA-CC1.
All wiring is supervised and power-limited unless otherwise noted.
Install a PAM-1 or equivalent listed relay only when you are required to
supervise the 200 mA AUX circuit wiring.
Configure Sense 1 and Sense 2 operation for Genesis Master mode and NAC
operation for “continuous.” See the documentation received with the
auxiliary/booster supply for details.
Use a CC1S if you want to maintain signal synchronization across multiple
auxiliary/booster supplies on the same Signature loop.