Chapter 7: Service and troubleshooting
EST3X Technical Reference Manual 215
Table 65: Signature Series mapping errors diagnostics
Problem
Suggested corrective action
The mapping command fai
led either because
the sensor did not draw current or it was not
possible to obtain stable mapping data from the
signaling line circuit
Verify that wiring is correct
Verify that devices are operational
Review the Chain Response and Device
Response lists
on the Device Chains tab to
identify the failed devices
Check for loose wiring connections at the
devices or T-taps
Check for faulty device(s)
While mapping a chain from a device bac
k to
the
Signature loop controller, the chain was
built with holes in it
Review the Chain Response and Device
Response lists
on the Device Chains tab to
identify the failed devices
Compare the serial numbers in the Chain
Response and Device Response lists on
the Device Chains tab
with the actual wiring
to identify a conflict
M
ap tables are inconsistent Upload the current map
Compare the current map with the
expected map
Write the map back to the loop controller
Ensure loop wiring is correct
Th
e actual Signature data loop map does not
match the expected map
Compare the current map with the
expected map
Write the map back to the loop controller
Ensure loop wiring is correct
Device address assignment failed
Review the serial number or address; if
missing, replace the device
The map in use has invalid data
(map
supervision failure)
Wait for automatic map reconstruction to
complete before continuing
Mapping supervision detected a change on the
loop
(a map rebuild was scheduled)
Wait for automatic map reconstruction to
complete before continuing
Mapping supervision detected the device
address or short address of the device being
supervised changed
(a map rebuild was
schedu
led)
Wait for automatic map reconstruction to
complete before continuing
The m
apping command failed because the
sensor did not draw current
, or it was not
possible to obtain stable mapping data from the
loop
(a map rebuild was scheduled)
Wait for automatic map reconstruction to
complete before continuing
Check for loose wiring
Check for a defective device