Chapter 7: Service and troubleshooting
EST3X Technical Reference Manual 227
7. From the Delay list, set the interval at which diagnostic updates will be
received.
8. Click Connect.
9. Click each tab to view the diagnostic results.
Trouble Tables diagnostics
The Trouble Tables analog addressable diagnostics tool displays multiple
categories of active device troubles. The active troubles should be compared
with a device’s trouble history (Device Trouble tab) to determine any possible
trouble pattern.
Click the Trouble Tables tab to see the list of active device troubles. Press F1 to
open the Trouble Tables Help topic, which provides instructions and descriptions
for the information provided.
The Device Address, Loop, and Label columns on the Trouble Tables list the
address, loop, and label of the sensor and module talking to the 3-AADC1 analog
addressable controller. The total number of communicating devices should equal
the number of installed devices. If the total is less then the number of installed
devices, see the Communications Fault column for missing devices or devices
not connected. If the total is higher then the number of installed devices, see the
Unexpected Fault column to identify extra device(s) installed on the loop.
Table 71 describes analog addressable device faults reported by the analog
addressable controller and their possible causes.
Table 71: Trouble Tables for analog addressable device faults
Trouble Table c
olumn Description Possible causes
Internal Fault
The device is reporting an
internal problem
The device is defective
Type Fault
It is the wrong device type for
the current configuration
Two device addresses are transposed
Duplicate Fault
Two or more devices have
the same address
If th
e total number of communicating
devices equals those installed,
there
is a duplicate device address
If the total number of communicating
devices is less then the number of
installed devices and a
communications fault is reported,
the device in the Communications
Fault column is addressed at the
location shown in the Duplicate
Fault column