B. Parameters and data of the CPX terminal
B−38
Festo P.BE−CPX−SYS−EN en 0902e
System data: Handheld
Function no. 0
Description Specifies whether or not a handheld is connected.
Bit Bit 5
Values
Bit 5
0
1
Handheld
Description
Handheld not connected
Handheld connected
[Handheld]
[connection OK]
Note Information for the higher−order controller
If necessary for test purposes, a parametrisation carried out by handheld is to be
cancelled by reloading the parameters, or forcing by higher−order PLC/IPC is to
be blocked whilst a handheld is connected.
Tab.B/50: Handheld
System data: Force mode
Function no. 0
Description Specifies whether Force is blocked or enabled.
Bit Bit 6
Values
Bit 6
0
1
Force mode
Description
Disabled
Enabled
[Force mode]
[Disabled]
[Enabled]
Note See also system parameter Force mode."
Tab.B/51: Force mode