8. Click the Preview switch to ON.
This switches the sensor into a color-coded preview mode that allows you to verify that your
calibration was successful.
9. If you are not satisfied with the calibration numbers or the height is zero, click Auto-Calibrate to
try the calibration again.
Note: To ensure consistency, perform auto calibration
several times to make sure that the sensor is returning
consistent (not exact) information.
10. If calibration numbers seem repeatedly inaccurate, or if you cannot fit the green box into an area
of the floor:
a. Select Calibration Preview, if not already enabled.
b. Manually set the sensor height and rotation to achieve an acceptable calibration image.
c. Save the results.
11. Adjust the Advanced Settings as necessary.
Field Description
Zoom Level
Select whether to use digital zoom of 20%, 40%, 60%, 80%, or 100%. Note that
saving a new zoom level requires a recalibration of the sensor. Zones may need to
be reconfigured.