19.  Analog  Outputs  (J22):    This  connector  is  factory-wired  to  the  terminal  block 
between pins 17 and 20. 
 
20.  Alarm Contacts Connector, 9 Pins (J18): The Gas High, Gas High-High and System 
OK  alarm  relays  are  factory-wired  from  this  connector  to  the  terminal  block 
between pins 7 and 15.  A three-wire type-C (Normally Open + Normally Closed + 
Common) set of contacts is available for each alarm.  
Note:  The System OK alarm relay is normally energized.  When a system fault occurs, 
it  de-energizes  the  relay.    Thus,  the  Normally  Open  (NO)  contact  actually  opens  on 
system failure or power loss.  See Chapter 11 for a description of the Hydran alarms. 
 
21.  AC Supply Fuses (F11):  There is one fuse holder for standard 5 x 20 mm fuses (the 
rating can be found in Section 14.9). 
 
22.  AC  Supply  Connector,  3  Pins  (J2):    The  AC  line  is  factory-wired  from  the  AC 
terminal block to this connector. 
 
23. Heater  Connector,  6  Pins  (J3):    The  enclosure  heater  is  factory-wired  to  the 
connector J3.  It consists of two 50-W resistors located under the support bracket 
of the electronic circuit board. 
 
24.  Voltage Selector Switch (SW1):  For wiring details, see a:  The  voltage  selector  is 
factory-selected and configured as per user requirements 
25. Table D - 12 in Appendix D. This selector is used to choose between the following:  
•  115 V, corresponding to 100–120 VAC 50/60 Hz  
•  230 V, corresponding to 200–240 VAC 50/60 Hz  
 
26.  Configuration Communication Status Indicator, Yellow (DS7):  This LED, only used 
for programming purposes at the factory, indicates there is a configuration of the 
unit  through  one  of  the  serial  ports.    It  flickers  as  data  bits  pass  through  the 
H201Ci-1,  whatever  the  direction  and  the  port  (RS-232,  RS-485  LAN,  USB  or 
optional modem). 
 
27.  Communication  Status  Indicator,  Yellow  (DS6):    This  LED  indicates  that  serial 
communication  activity  is  present.    It  flickers  as  data  bits  pass  through  the 
H201Ci-1,  whatever  the  direction  and  the  port  (RS-232,  RS-485  LAN,  USB  or 
supervisory link). 
 
28.  Alarm  1  High  Latch  Indicator,  Red-Orange  (DS5):    This  LED  indicates  that  the 
operator  did  not  acknowledge  the  alarm  1  (Gas  High).    It  is  impossible  to 
acknowledge the alarm if it is still active. 
 
29.  Alarm 2 High-High Latch Indicator, Red-Orange (DS4):  This LED indicates that the 
operator  did  not  acknowledge  the  alarm  2  (Gas  High-High).    It  is  impossible  to 
acknowledge the alarm if it is still active.