5.1.5.2 Failure register / Acknowledging alarms
Display of the failure register
- SelecttheparameterFailure registerintheSPECFUNCTIONSmenu.
- PressE.Thelasterrorthathasoccurredwillbedisplayed.
- Usingthekey+itispossibletodisplaythepreviousalarm.
- Thefailureregistercantakeupto10values.Ifanewfailureisreported,theoldestentryinthefailureregister
isoverwritten.
- Theentriesinthefailureregisterareretaineduntiltheregisteriscleared.
- PressingEthetimewhenthealarmoccurredwillbedisplayed.Thetimereferstotheconverterfunctioning
period(presenceofthesupplyvoltage).
- Afterdisplaying,themenugoesbackautomaticallytotheFailure register point.
- BypressingthekeyCANCduringthealarmdisplay,theinterventiontimeisnotshownbutonthecontrary
yougobacktotheFailure register menu.
SPEC FUNCTIONS
Failure register
Failure register
External fault
Failure register
237 hours 45 min
Failure register
Undervoltage
Failure register
76 hours 23 min
Failure register
Overtemp motor
Failure register
8 hours 06 min
max 10
E
CANC
CANC
CANC
E
E
E
+
-
+
-
+
-
Clearing the failure register
SPEC FUNCTIONS
Failure reg del
Failure reg del
Ready
E
- SelecttheparameterFailure reg del intheSPECFUNCTIONSmenu.
- PressE.Thefailureregisteriscleared.