—————— Instruction manual ——————
177
Parameter description No.
Value
Standard
Conguration
min max
Factory
American
Factory
Standard
Flux reg mode
Constantcurrent(0)
Voltagecontrol(1)
Externalcontrol(2)
ExtdigitalFC(3)
ExtwiredFC(4)
469 0 4 Const.current(0) Const.current(0) -
Enable ux weak
ON/OFF
498 0 1 1 1 *
Speed-0 f weak
ON/OFF
499 0 1 0 0
Flux reference [%]
500 0.0 100.0 0.0 0.0 **
Flux current [%]
234 0.0 100.0 - - **
Out vlt level
921 0.00 100.0 100.0 100.0 **/***
FC cur ref hyst
1522 1 100 5 5
I eld cnst 40
916 0.0 100.0 40.0 40.0
I eld cnst 70
917 0.0 100.0 70.0 70.0
I eld cnst 90
918 0.0 100.0 90.0 90.0
Set ux / if
919 0 1 0 0
Reset ux / if
920 0 1 0 0
Nom ux curr [A]
374 0.5 80.0 S S
Motor nom ux
280 0.00 P374 P374 P374
FC limit ramp
Disabled(0)
Enabled(1)
411 - - Disabled Disabled
FC lmt ramp time [ms]
888 200 10000 800 800
*Thisfunctioncanbesetonaprogrammabledigitalinput.
** Thisparametercanbesetonaprogrammableanalogoutput.
*** Thisparametercanbesetonaprogrammableanaloginput.
Enable ux reg Enablingoftheeldconverter
ON FieldconverterEnabled
OFF FieldconverterDisabled.Theeldcurrentiszero.
Flux reg mode Operatingmodeoftheeldconverter.
Constantcurrent Themotoreldworkswithaconstantcurrent.Thecurrentvalue
correspondstothesettingoftheMotor nom ux parameter.
IfanycurveviatheI eld cnstparameterswillbedened,
thisvaluecanbechangedlinearly,throughMotor nom ux
(percentageofnominaluxMotor nom ux)
(seeFlux/ifcurveparagraph5.4.5)
Voltagecontrol Themotoreldisregulatedwithacombinationoftorqueand
constantpower(armatureandeldregulation--eldweaken-
ing).ViatheMax out voltageparameterintheCONFIGURA-
TIONmenu,issetthemax.armaturevoltage.
WhenEnable fbk bypass(PAR458)isenabled(default)the
Voltage control selectionisdisabled.
Externalcontrol Theeldissuppliedthroughanexternalexcitation(rectier/
eldconverter).
ExtdigitalFC SettingrequiredforeldcontrolbyTPD32EV-FCwithuseof
opticalberconnection.
ExtwiredFC SettingrequiredforeldcontrolbyTPD32EV-FCwithuseof
standarddigitalandanalogI/Os.
note! FluxregmodesExt digital FCandExt wired FCusesameeldweakening
regulationofuxregmodeVoltage control.
Ext wired FC controlmodecannot beselectedbeforeyou havecorrectly