EasyManua.ls Logo

Heraeus Electro-Nite CasTemp Wireless - Implemented Protocols List; Non-Standard Protocols; Binding Protocols and Telegrams

Heraeus Electro-Nite CasTemp Wireless
117 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 June 2020 CasTemp Wireless including CasTemp Superheat Page 48
6.2.1 TCP/IP Client
When the TCP-IP client is selected from the physical device options’ menu (Figure 50). Figure 52
shows the configuration window after TCP/IP Client is selected.
Figure 52: TCP/IP Client configuration
Following settings are user configurable:
• Name of the interface – choose a name that will be shown in the physical device list
• IP Address: server IP Address
• Port: server port to which the client must connect to
• Keep socket open: Client has a permanent connection to the server and does not only
connect when it has data.
• Use for input – required for Superheat see section 9.4
6.2.2 TCP-IP Server
The CasTemp Wireless instrument can also be configured as a TCP/IP server. When the TCP-IP
server is selected from the physical device options’ menu (Figure 50). Figure 53 shows the
configuration window after TCP/IP server is selected.
The following settings are user configurable:
• Name of the interface – choose a name that will be shown in the physical device list
• Port: server port that is opened on the CasTemp wireless instrument to which the client must
connect to
• Maximum concurrent client connections: the maximum number of clients the server can
accept
• Buffer size
• Use for input – required for Superheat see section 9.4
Figure 53: TCP/IP Server configuration

Table of Contents