EasyManua.ls Logo

Heraeus Electro-Nite CasTemp Wireless - Telegram Output Formats

Heraeus Electro-Nite CasTemp Wireless
117 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 June 2020 CasTemp Wireless including CasTemp Superheat Page 50
6.2.4 Profibus
The CasTemp Wireless instrument is also able to communicate using the Profibus interface. To add a
Profibus interface, select the Profibus (HMS) interface from the drop down shown in the physical
device options’ menu (Figure 50), Figure 56 appears.
Figure 56: Profibus configuration window
Following settings are user configurable:
Name: only used for internal instrument reasons
COM Port: should always be COM2
Node ID: PLC has to know the node ID. Each node ID has to be unique for the PLC.
Type. Refer to Anybus module card,
Use for input required for Superheat see section 9.4
Note: Heraeus Electro-Nite personnel will provide a GSD file for the PLC to configure the Profibus
successfully.
6.2.5 EtherNet IP
The CasTemp Wireless instrument is also able to communicate using the EtherNet IP interface. To
add an EtherNet IP interface, select the EtherNet IP (HMS) interface from the drop down shown in the
physical device options’ menu (Figure 50), Figure 57 appears.
Figure 57: EtherNet IP Configuration window
Following settings are user configurable:
Name: only used for internal instrument reasons
COM Port: should always be COM2
IP Address: PLC IP Address
Subnet: PLC subnet
Use for input required for Superheat see section 9.4
An EDS file for the PLC is required to connect and to configure successfully.

Table of Contents

Related product manuals