IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021 87
Programming Menu Quick Reference Programming Overview
1. Available on Internal SLC.
2. Available with SLC Family as SK.
Family as IDP.
3 Available with SLC Family as SD.
4. Requires wireless gateway.
5. AUX SYNC setting is only applicable for the B200S /IV Sounder Base.
Time Options
Water Flow Delay 0 - 90 Seconds *1 sec
Water Flow delay is the
number of seconds
before a water flow
alarm is generated.
Section 9.6.2
Alarm Verify 60 to 250 seconds *60 sec
Low AC Report Time 0 - 30 hours *3 hrs
AC Freq:
50 Hz
*60Hz60 Hz
Internal
Clock Display Format
AM/PM
*AM/PM
MIL
Auto-resound
4 hours
*24 hours
24 hours
Miscellaneous
Options
SYNC Strobes when
Silenced
Y
*N
Section 9.6.5
N
Auto Display Events
Y
*N
N
Daylight Saving
Options
Auto Daylight Saving
Time
Y
*Y
Section 9.6.6
N
DST Start
Select week: 1st, 2nd, 3rd, 4th or Last Select month
DST End
Edit Banner Refer to Appendix B Section 9.6.7
SLC Family
IDP
Section 9.6.8SD
SK
Jump
Start
AutoPrg
Y (Yes)
N (No)
Section 9.15
Restore
Defaults
Y (Yes)
N (No)
Section 9.8
*Default
Menu Options/Defaults Comments
Table 8.4 Programming Quick Reference List (Continued)