Configuration
Function Prompt Selections or
Parameter
Lower Display
Range of Setting
Upper Display
Definition
values.
NOTE 5. Thermocouple Warning means that the
instrument has detected that the Thermocouple Input
is starting to fail. Not valid for other input types.
NOTE 6. Thermocouple Failing means that the
instrument has detected that the Thermocouple Input
is in imminent danger of failing. Not valid for other
input types.
NOTE 7: For the Digital Input selections, DIG INP1
can be either enabled or disabled in the Options
Group (See Sub-Section 3.12), but DIG INP2 must
be enabled in the Options Group for the alarm to
function properly.
A1S1 H L
If Setpoint Programming is disabled or if the
Alarm Type is not configured for Event On/Off:
ALARM 1 SETPOINT 1 STATE—Select whether
you want the alarm type chosen in prompt
A1S1TYPE to alarm High or Low.
HIGH
LOW
HIGH ALARM
LOW ALARM
A1S1 EV
If Setpoint Programming is enabled and if the
Alarm Type is configured for Event On/Off:
ALARM 1 SEGMENT EVENT 1—Select whether
you want the alarm type chosen in prompt
A1S1TYPE to alarm the beginning or end of a
segment in setpoint Ramp/Soak programming.
BEGIN
END
BEGINNING OF SEGMENT
END OF SEGMENT
ATTENTION Alarms configured for events will not
operate on Setpoint Program segments of zero
length.
12/04 UDC3200 Universal Digital Controller Product Manual 89