Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
A1S2TYPE 
Same as A1S1 TYPE 
ALARM 1 SETPOINT 2 TYPE—Select what you 
want Setpoint 2 of Alarm 1 to represent. 
The selections are the same as A1S1TYPE. 
A1S2 H L 
HIGH 
LOW 
ALARM 1 SETPOINT 2 STATE—Same as 
A1S1 H L. 
A1S2 EV 
BEGIN 
END 
ALARM 1 SEGMENT EVENT 2—Same as A1S1 
EV. 
A2S1TYPE 
Same as A1S1 TYPE 
ALARM 2 SETPOINT 1 TYPE—Select what you 
want Setpoint 1 of Alarm 2 to represent. 
The selections are the same as A1S1TYPE. 
 ATTENTION   Not available with Relay Duplex or 
Position Proportional output types unless using Dual 
Relay PWA. 
A2S1 H L 
HIGH 
LOW 
ALARM 2 SETPOINT 1 STATE—Same as 
A1S1 H L. 
A2S1 EV 
BEGIN 
END 
ALARM 2 SEGMENT EVENT 1—Same as A1S1 
EV. 
A2S2TYPE 
Same as A1S1 TYPE 
ALARM 2 SETPOINT 2 TYPE—Select what you 
want Setpoint 2 of Alarm 2 to represent. 
The selections are the same as A1S1TYPE. 
ATTENTION Not applicable with Relay Duplex or 
Position Proportional output types unless using Dual 
Relay PWA. 
A2S2 H L 
 
HIGH 
LOW 
ALARM 2 SETPOINT 2 STATE—Same as 
A1S1 H L. 
A2S2 EV 
BEGIN 
END 
ALARM 2 SEGMENT EVENT 2—Same as  
A1S1 EV. 
ALHYST 
0.0 to 100.0 % of span or 
full output as appropriate 
ALARM HYSTERESIS—A single adjustable 
hysteresis is provided on alarms such that when the 
alarm is OFF it activates at exactly the alarm 
setpoint; when the alarm is ON, it will not deactivate 
until the variable is 0.0 % to 100 % away from the 
alarm setpoint. 
Configure the hysteresis of the alarms based on 
INPUT signals as a % of input range span. 
Configure the hysteresis of the alarm based on 
OUTPUT signals as a % of the full scale output 
range. 
90  UDC3200 Universal Digital Controller Product Manual  12/04