Output Calibration
Step Description Press Action
2
Select Automatic or
Manual Calibration
Function
FunctionFunction
until you see:
Upper Display = DISABLE
Lower Display = POS PROP
You can calibrate the controller output manually or let the
controller calibrate the output automatically.
If the slidewire has never been calibrated, you must use
DO AUTO first. In the “Automatic Calibration Mode” (DO
AUTO), the controller relays automatically move the motor
in the proper direction.
If desired, however, the motor may be manually positioned
to 0 % and 100 % positions. Disconnect the relay wires.
Use DO MAN. In the “Manual Calibration Mode” (DO
MAN), the motor does not move. Instead, the existing 0 %
and 100 % values may be changed with the
or
key.
to select automatic or manual calibration.
Upper Display = DO AUTO or DO MAN
Lower Display = POS PROP
If you select… Then…
DO AUTO go to Step 3
DO MAN go to Step 5
ATTENTION
When calibration is terminated, this
selection reverts to DISABL.
3 DO AUTO
Set 0 % value
Function
FunctionFunction
The decrement relay is turned on to move the motor to 0 %
position.
Upper Display =
(counts of slidewire feedback 0-3000)
Lower Display = ZERO VAL
When the motor stops, the display should stop counting,
then go to the next step.
4 DO AUTO
Set 100 % value
Function
FunctionFunction
The increment relay is turned on to move the motor to
100 % position.
Upper Display =
(counts of slidewire feedback 0-3000)
Lower Display = SPAN VAL
When the motor stops, the display should stop counting,
then, go to Step 8.
5 DO MAN
Set 0 % value
You will see:
Upper Display =
(the existing zero calibration value in counts))
Lower Display = ZERO VAL
or
Function
FunctionFunction
12/04 UDC3200 Universal Digital Controller Product Manual 149