Configuration 
Function Prompt   Selections or  
Parameter  
Lower Display 
Range of Setting  
Upper Display 
Definition 
CYC SEC 
or 
CYC SX3 
1 to 120 
CYCLE TIME (HEAT) determines the length of one 
time proportional output relay cycle. Defined as 
"HEAT" cycle time for Heat/Cool applications. 
CYC SEC—Electromechanical relays 
CYC SX3—Solid state relays 
 ATTENTION  Cycle times are in either second or 
1/3-second increments depending upon the 
configuration of RLY TYPE in the Output Algorithm 
Set Up group. 
CYC2 SEC 
or 
CYC2 SX3 
1 to 120 
CYCLE TIME 2 (COOL) is the same as above 
except it applies to Duplex models as the cycle time 
in the "COOL" zone of Heat/Cool applications or for 
the second set of PID constants. 
CYC2 SEC—Electromechanical relays 
CYC2 SX3—Solid state relays 
 ATTENTION  Cycle times are in either second or 
1/3-second increments depending upon the 
configuration of RLY TYPE in the Output Algorithm 
Set Up group. 
SECURITY 
0 to 9999 
SECURITY CODE—The level of keyboard lockout 
may be changed in the Set Up mode. Knowledge of 
a security code may be required to change from one 
level to another. This configuration should be copied 
and kept in a secure location. 
NOTE: The Security Code is for keyboard entry only 
and is not available via communications. 
 ATTENTION  Can only be changed if LOCKOUT 
selection is NONE. 
LOCKOUT 
 
LOCKOUT applies to one of the functional groups: 
Configuration, Calibration, Tuning, Accutune. DO 
NOT CONFIGURE UNTIL ALL CONFIGURATION 
IS COMPLETE. 
 
NONE 
NONE—No lockout; all groups are read/write. 
 
CALIB 
CALIB—All groups are available for read/write 
except for the Calibration and Keyboard Lockout 
groups. 
 
+ CONF 
+ CONF—Tuning, SP Ramp, and Accutune groups 
are read/write. All other groups are read only. 
Calibration and Keyboard Lockout groups are not 
available. 
 
+ VIEW 
+ VIEW—Tuning and Setpoint Ramp parameters are 
read/write. No other parameters are viewable. 
42  UDC3200 Universal Digital Controller Product Manual  12/04