25: DEVICENET SLAVE MODULE
25-6 OPENNET CONTROLLER USER’S MANUAL
DIP Switch Settings
DIP switches are inside the protective lid. After setting the DIP
switches, replace the lid into position.
All DIP switches are set to off before shipping from factory.
Set the DIP switches to select the node address (MAC ID: media
access control identifier), data rate, output hold/load off, and physical
port number.
Do not set the DIP switches to the “Selection Prohibited” positions.
Node Address (MAC ID)
Node Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5
0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON
1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON
23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON
27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON
28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON
30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON
31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON
ON
12345678910
NO
H/L
DR1
DR0
NA5
NA4
NA3
NA2
NA1
NA0
u
pu
o
or
oa
Output/Load H/L
LOAD OFF OFF
HOLD ON
Physical Port Number
Physical Port Number NO
0 OFF
1 ON
a
a
a
e
Data Rate DR0 DR1
125k baud OFF OFF
250k baud ON OFF
500k baud OFF ON
(Selection Prohibited) ON ON
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com