26: LONWORKS INTERFACE MODULE
OPENNET CONTROLLER USERS MANUAL 26-7
Terminator
Terminators must be connected to the LONWORKS network. When setting up a network, connect one or two terminators
depending on the topology. The terminator consists of one resistor and two capacitors as illustrated below:
Bus Topology
Connect terminators to the both ends of the bus topology network.
Free Topology
Connect a terminator to any position on the free topology network.
R 105, 1%, 1/8W
C1 and C2 100 µF, 50V (note the polarity)
R 52.3, 1%, 1/8W
C1 and C2 100 µF, 50V (note the polarity)
+
R
C1
C2
Network
+
Terminator Configuration
Terminator Terminator
Node
Node
Node Node Node
Node Node
Terminator
Node
Node Node
Node
Node
Node
Node