13: BIT SHIFT / ROTATE INSTRUCTIONS
OPENNET CONTROLLER USERS MANUAL 13-5
ROTL (Rotate Left)
Valid Operands
For the valid operand number range, see page 6-2.
Internal relays M0 through M2557 can be designated as S1. Special internal relays cannot be designated as S1.
The quantity of bits to rotate can be 1 through 15 for the word data type, or 1 through 31 for the double-word data type.
Since the ROTL instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction
should be used as required.
Valid Data Types
When a bit operand such as Q (output), M (internal relay), or R (shift register) is designated as the source, 16 points (word
data type) or 32 points (double-word data type) are used.
When a word operand such as D (data register) or L (link register) is designated as the source, 1 point (word data type) or
2 points (double-word data type) are used.
Operand Function I Q M R T C D L Constant Repeat
S1 (Source 1) Data for bit rotation X X —— XX ——
bits Quantity of bits to rotate ————————1-15, 1-31
W (word) I (integer) D (double word) L (long)
X X
Before rotation: 1 0 1010 1 0 1 1 1101 0 0
CY
M8003
MSB LSB
S1
1After rotation: 0 1010 1 0 1 1 1101 0 0
CY
M8003
MSB LSB
S1
1
Rotate to the left
S1
*****
bits
**
When input is on, 16- or 32-bit data of the designated source operand S1 is
rotated to the left by the quantity of bits designated by operand bits.
The result is set to the source operand S1, and the last bit status rotated out is set
to a carry (special internal relay M8003).
ROTL(*)
• Data Type: Word (bits to rotate = 1)
Before rotation:
1 0 1010 1 0 1 1 1101 0 0
CY
M8003
MSB LSB
S1
1
After rotation:
10 1010 1 0 1 1 1101 0 0
CY
M8003
MSB LSB
S1
Rotate to the left
10 1010 1 0 1 1 1101 0 0
1 0 1010 1 0 1 1 1101 0 0
• Data Type: Double Word (bits to rotate = 1)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC OpenNet series and is the answer not in the manual?

IDEC OpenNet series Specifications

General IconGeneral
BrandIDEC
ModelOpenNet series
CategoryController
LanguageEnglish

Related product manuals