2: MODULE SPECIFICATIONS
OPENNET CONTROLLER USER’S MANUAL 2-27
FC3A-T32K5 (32-point Transistor Sink Output Module) — Fujitsu Connector Type
Applicable Connector: FCN-367J040-AU (Fujitsu)
Wiring Schematic
• COM terminals are connected together internally.
• Terminal numbers are the front view of the male connector on the output module.
• For wiring precautions, see page 3-6.
0
1
2
3
4
5
6
7
10
11
12
13
14
15
16
17
20
21
22
23
24
25
26
27
30
31
32
33
34
35
36
37
Tr
OUT
Terminal No. Name
B20 Q0
B19 Q1
B18 Q2
B17 Q3
B16 Q4
B15 Q5
B14 Q6
B13 Q7
B12 Q10
B11 Q11
B10 Q12
B9 Q13
B8 Q14
B7 Q15
B6 Q16
B5 Q17
B4 NC
B3 NC
B2 +V
B1 +V
Terminal No. Name
A20 Q20
A19 Q21
A18 Q22
A17 Q23
A16 Q24
A15 Q25
A14 Q26
A13 Q27
A12 Q30
A11 Q31
A10 Q32
A9 Q33
A8 Q34
A7 Q35
A6 Q36
A5 Q37
A4 NC
A3 NC
A2 COM(–)
A1 COM(–)
L
Terminal No. Name
B20 Q0
B19 Q1
B18 Q2
B17 Q3
B16 Q4
B15 Q5
B14 Q6
B13 Q7
B12 Q10
B11 Q11
B10 Q12
B9 Q13
B8 Q14
B7 Q15
B6 Q16
B5 Q17
B4 NC
B3 NC
B2 +V
B1 +V
L
L
L
L
L
L
L
L
L
L
L
L
L
Load
L
L
Terminal No. Name
A20 Q20
A19 Q21
A18 Q22
A17 Q23
A16 Q24
A15 Q25
A14 Q26
A13 Q27
A12 Q30
A11 Q31
A10 Q32
A9 Q33
A8 Q34
A7 Q35
A6 Q36
A5 Q37
A4 NC
A3 NC
A2 COM(–)
A1 COM(–)
Fuse
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Load
L
L
+ –
Connect the two +V terminals together, and connect the two COM(–) terminals together because
the current capacity of one terminal is exceeded when many outputs are on simultaneously.
B20
B19
B18
B17
B16
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
A20
A19
A18
A17
A16
A15
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com