HD2 Series Inverter Function Parameter List
-160-
Function
code
Name
Description
Default
value
Modify
P04.24
High-frequency
oscillation control
factor of motor 2
unstable running of motors or even overcurrent of
inverters. You can modify this parameter to
prevent current oscillation.
Setting range of P04.23: 0–100
Setting range of P04.24: 0–100
Setting range of P04.25: 0.00 Hz–P00.03 (Max.
output frequency)
10
P04.25
Oscillation
control threshold
of motor 2
30.00Hz
P04.26
Energy-saving
run
0: No action
1: Automatic energy-saving operation
Under light-load state, the motor can adjust the
output voltage automatically to achieve
energy-saving purpose
0
P04.27
Voltage setting
channel
0: Keypad; output voltage is determined by P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step (the set value is determined by P10
group)
6: PID
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: HDIB
11: EtherCAT/PROFINET/EtherNet IP
communication
12: Programmable card
13: Reserved
0
P04.28
Voltage value set
through keypad
When the channel for voltage setup is set to
"keypad", the value of this function code is digital
voltage set value.
Setting range: 0.0%–100.0%
100.0%
P04.29
Voltage increase
time
Voltage increase time means the time needed
from outputting the min. voltage to accelerating to
output the max. voltage.
Voltage decrease time means the time needed
from outputting max. voltage to outputting the min.
voltage
5.0s
P04.30
Voltage decrease
time
5.0s