HD2 Series Inverter Function Parameter List
-162-
Reactive current
closed-loop
integral time in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the integral
coefficient of the reactive current closed-loop
control.
Setting range: 0–3000
Reactive current
closed-loop
output limit in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the output
limit of the reactive current in the closed-loop
control. A greater value indicates a higher reactive
closed-loop compensation voltage and higher
output power of the motor. In general, you do not
need to modify this parameter.
Setting range: 0–16000
Enable/disable IF
mode for
asynchronous
motor 1
Current setting in
IF mode for
asynchronous
motor 1
When IF control is adopted for asynchronous
motor 1, this parameter is used to set the output
current. The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0–200.0%
Proportional
coefficient in IF
mode for
asynchronous
motor 1
When IF control is adopted for asynchronous
motor 1, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0–5000
Integral
coefficient in IF
mode for
asynchronous
motor 1
When IF control is adopted for asynchronous
motor 1, this parameter is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0–5000
Starting
frequency point
for switching off
IF mode for
asynchronous