HD2 Series Inverter Function Parameter List
-204-
Enable inverter
overload integral
0: Disabled
1: Enabled
When this parameter is set to 0, the overload
timing value is reset to zero after the inverter is
stopped. In this case, the determination of inverter
overload takes more time, and therefore the
effective protection over the inverter is weakened.
When this parameter is set to 1, the overload
timing value is not reset, and the overload timing
value is accumulative. In this case, the
determination of inverter overload takes less time,
and therefore the protection over the inverter can
be performed more quickly.
VF vibration
control method
0x00–0x11
Ones place:
0: Method 1
1: Method 2
Tens place:
0–1: Reserved
SPO switch-on
detection delay
time
0.0–60.0(s)
Note: The SPO detection is started only after the
inverter runs for the delay time P11.28 to advoid
false alarms caused by the unstable frequency.
5.0 ○
factor
P11.30 Reserved 0 0
●
P11.31
Fault severity
group 1
0x0000–0x3333
Thousands place/Hundreds place/Tens
place/Ones place:
0: Report the fault
1: Report the fault after deceleration to stop
2: Pre-alarm, with the action executed according
to P11.51
3: Screen out the fault
Note: Different fault actions are taken for different
fault severities. The first 10 faults are not grouped
by severity, but each four of the subsequent faults
are grouped by severity in ascending order from
right to left in hexadecimal format, that is, from the
ones place to the thousands place (for example,
the ones place of fault severity group 1
corresponds to fault 11).
Group 1: Faults 11–14 (OL1, OL2, SPI, SPO)
0x0000 ○
P11.32
Fault severity
group 2
0x0000 ○
P11.33
Fault severity
group 3
0x0000 ○
P11.34
Fault severity
group 4
0x0000 ○
P11.35
Fault severity
group 5
0x0000
○
P11.36
Fault severity
group 6
0x0000
○
P11.37
Fault severity
group 7
0x0000
○
P11.38
Fault severity
group 8
0x0000
○
P11.39 Fault severity 0x0000 ○