9 Communication 9.6.3 CANlink Software Conguration
b) The
CANlink Cong
icon is displayed. Double-click
CANlink Cong
. The
CANlink3.0 Cong
Wizard
page is displayed, as shown in the following gure.
Baud Rate
(required)
Eight options are available for different scenarios: 20 Kbps, 50 Kbps, 100 Kbps, 125 Kbps, 250 Kbps,
500 Kbps, 800 Kbps, and 1 Mbps. You can select the desired option in the drop-down box, and then
download the conguration to the master station (this parameter is valid for the master station only, and
needs to be manually modied on a slave station). You can select the baud rate based on the bus load and
communication distance.
Net Heartbeat
(optional)
All slave stations send heartbeats to the master station at a specied interval. The master station monitors
the state (online or ofine) of each slave station through the heartbeat mechanism. Slave stations monitor
the state of the master station through its heartbeats. (It is recommended that the interval be more than 200
ms.) If you deselect this parameter, the heartbeat function is disabled and the system cannot monitor the
network.
Master Station No.
(required)
In this example, the master station number is the number of the PLC that serves as a master station. The
number cannot be changed. If the number entered is inconsistent with the actual number, the PLC will
determine that the downloaded conguration is invalid. For example, if you enter 7, the conguration is valid
only when downloaded to station 7. Station 7 then assigns the conguration to other stations. The CANlink
network conguration is downloaded to the master station and then assigned to slave stations. In this way,
the system can monitor and manage the entire network through the master station in the background.
Master Station
Synchronous Write Trigger Element
(optional)
It is an element triggering Synchronous Write for the master station. When a trigger element (M) is set, the
corresponding conguration takes effect. The element is automatically reset after data is sent.