10 Extension Modules
10.2.4 Analog Input Module (AM600-4AD)
External wiring
Analog input wiring diagram
+15V
15V
450k
¡
450k
¡
*2
*1Shield grounding
V+
V-
I+
+15V
15V
450
k
¡
450k
¡
*2
*
1
V+
V
-
I+
*5
*
3
250¡
*4
AGND
AGND
FG
(a)
Voltage input
(b)
Current input
24V
COM
+15V
-15V
+24V
DC/DC
conveter
fliter
24Vdc
external
power
AGND
AGND
Shield grounding
Must be
connected
Input impedance
Input impedance
Use 2-core shielded twisted pair cable for analog signal.
Indicates input impedance of 4AD.
For current input, terminal (V+) must be connected to terminal (I+).
When the input signal is a differential signal, "AGND" can be connected to analog ground of compatible devices to
eliminate the difference of common mode voltage between devices and ensure the accuracy of module sampling.
The module should be mounted on a well-grounded metal bracket, and ensure that the metal shrapnel at the
bottom of the module is in good contact with the bracket.
(3) Wiring precautions
Do not bundle the cable together with AC cable, main lines, high voltage cable and so forth; otherwise,
it may result in an increased noise, surge and induction.
Apply single-point grounding for the shielding of shielded cable and solder sealed cable.
Tubed and solderless crimp terminal cannot be used with terminal block. Using marking sleeve or
insulation sleeve to cover the cable connector part of the crimp terminals is recommended.