EasyManuals Logo

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
JOHNSON CONTROLS
104
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 5 – SEQUENCE OF OPERATION
• When the current building pressure is less than the
building pressure setpoint plus the building pres-
sure control offset, the exhaust fan is turned OFF.
Modulating Damper - VFD
• This power exhaust type is used for two different
sequences:
1. Modulating damper with single speed ex-
haust fan
2. Modulating exhaust fan with barometric
damper
• How the unit operates is based on how it was or-
dered. Both of these sequences utilize the exhaust
damper output for controlling the exhaust fan.
1. Modulating damper with single speed exhaust
fan: The 0–10 VDC signal is sent from the ex-
haust damper output to the exhaust damper ac-
tuator.
2. Modulating exhaust fan with barometric
damper: The 0–10 VDC signal is sent from
the exhaust damper output to the exhaust fan
VFD.
• The 0–10 VDC signal sent from the IPU board
directly correlates to a 0–100% damper position
or VFD speed.
1. Modulating damper with single speed ex-
haust fan: For example, a 2.5 VDC signal is
an exhaust damper position of 25%.
2. Modulating exhaust fan with barometric
damper: For example, a 2.5 VDC signal is an
exhaust fan VFD speed of 25%.
Modulating Damper with Fixed Speed
Exhaust Sequence of Operation
• Power exhaust type must be set to Modulate Damp-
er - VFD in the OPTIONS-EXHAUST menu.
• Building pressure setpoint must be set in the SET-
POINTS-EXHAUST menu.
• Exhaust output for fan start must be set in the
SETPOINTS-EXHAUST menu.
• Exhaust Output for fan stop must be set in the
SETPOINTS-EXHAUST menu.
• This sequence uses a modulating exhaust damper
with a single speed exhaust fan.
• When the current building pressure becomes
greater than the building pressure setpoint, the
IPU board starts sending a 0–10 VDC signal to
the exhaust damper actuator.
• When the exhaust damper position is greater than
the exhaust output for fan start, the exhaust fan is
turned ON.
• When the exhaust damper position is less than
the exhaust output for fan start, the exhaust fan is
turned OFF.
Modulating Exhaust Fan with Barometric
Damper
• Power exhaust type must be set to Modulate Damp-
er - VFD in the OPTIONS-EXHAUST menu.
• Building pressure setpoint must be set in the SET-
POINTS-EXHAUST menu.
• Exhaust output for fan start must be set in the
SETPOINTS-EXHAUST menu.
• Exhaust output for fan stop must be set in the
SETPOINTS-EXHAUST menu.
• When the current building pressure becomes
greater than the building pressure setpoint, the
IPU board starts sending a 0–10 VDC signal to
the exhaust fan VFD.
• Once the exhaust fan speed signal, (exhaust damp-
er position on the LCD screen) is greater than the
exhaust output for fan start, the exhaust fan VFD
is started.
• Once the exhaust fan speed signal (exhaust damp-
er position on the LCD screen) is less than the ex-
haust output for fan stop, the exhaust fan VFD is
stopped.
Exhaust Fan Control: BAS Sequence of
Operation
• The Series 100 units have the ability to allow a
BAS to control the exhaust fan assembly.
• This option allows a controls company to send a
BAS signal out to one or more Series 100 units,
which controls all exhaust fans at the same speed.
• Power exhaust type must be set to Modulate Damp-
er - VFD in the OPTIONS-EXHAUST menu.
• Exhaust control BAS must be User Enabled in the
SERVICE menu.

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals