EasyManuals Logo

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
JOHNSON CONTROLS
96
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 5 – SEQUENCE OF OPERATION
Freeze Protection
• On Series 100 units with hot water/steam coils, the
IPU board has a built in freeze protection sequence.
• The freeze protection sequence is not adjustable.
• There are two different sequences for freeze pro-
tection:
1. Supply fan ON, heating is inactive
1. When the supply fan is running, the IPU
board monitors the current SAT.
2. When the current SAT becomes equal to/
less than 38.0°F, the IPU board sends a 0–10
VDC signal to open the hot water/steam
valve to maintain the current SAT at 38.0°F.
2. Supply fan OFF, heating is inactive
1. When the supply fan is OFF, the IPU board
monitors the current OAT.
2. When the current OAT becomes equal to/
less than 40.0°F, the IPU board sends a 0–10
VDC signal to the hot water/steam valve to
fully open the valve.
Freeze Fault
• The IPU board monitors the status of the factory
installed freezestat.
• When the freezestat is ON (open), it closes on
when the temperature drops to 35.0°F.
• When the freezestat closes for 10 seconds, the IPU
board fully opens the hot water/steam valve, and a
WRN- TRIP FREEZESTAT is declared.
• The IPU starts a 5 minute Freeze Trip Timer.
• If at any time during this 5 minutes, the freezestat
returns to normal operation, open, the unit resumes
normal operation and the warning is cleared.
• If the freezestat remains closed for 5 minutes, the
IPU shuts down the unit and a Lockout-Hot Water
Freeze Fault is declared.
Heating Sequences
• The Series 100 unit has several different sequenc-
es associated with the different heating options.
• Each of these sequences can be User Enabled/User
Disabled in the PROGRAM-HEATING menu.
• They can also be User Enabled/User Disabled
through a BAS.
Morning Warm-Up
• Morning warm-up is a sequence that typically
warms a building to a comfortable temperature
before personnel arrive.
• The morning warm-up sequence on Series 100
units can only be started from an Unocc mode.
• Morning warm-up can be started either from the
IPU board internal schedule or from a BAS.
Morning Warm-Up Setup
• The Series 100 unit must have one of the op-
tional heating types installed.
• Morning warm-up must be User Enabled in
the PROGRAM-HEATING menu.
• Morning warm-up uses the current RAT to
determine if the heating source should be
turned ON.
Morning Warm-Up Sequence of Operation
• The current unit mode must be Unocc Stand-
by.
• A command for morning warm-up must be
received from either the BAS or the internal
clock schedule.
• Once the IPU board receives the morning
warm-up command, the supply fan starts (the
return fan also starts if installed).
• The supply fan is controlled as follows:
1. VAV or FlexSys: To the active duct stat-
ic pressure setpoint
2. SZVAV: At 100%
• After the supply is ON for 5 minutes, the IPU
board compares the current RAT to the active
RAT heating setpoint.
• When the current RAT is equal to/less than
the active RAT setpoint minus 1.0°F, the
unit’s heating source is turned ON.
• The heating source is controlled to the fol-
lowing setpoints:
1. VAV or FlexSys: SAT heating
2. SZVAV: 2nd stage heating

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals