EasyManuals Logo

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #97 background imageLoading...
Page #97 background image
JOHNSON CONTROLS
97
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
• The heating source is turned OFF when the
current RAT is equal to/greater than the ac-
tive RAT heating setpoint plus 0.5°F.
• The heating source is also turned OFF when
the morning warm-up command is removed
or the unit enters an Occ mode.
Adaptive Morning Warm-Up
Adaptive morning warm-up is only utilized when the
Series 100 unit is utilizing an internal programming
schedule to determine Occ/Unocc modes.
With adaptive morning warm-up, the IPU board calcu-
lates the start time to ensure that the RAT is within 0.5°F
of the RAT heating setpoint when the unit switches to
an Occ mode. This is accomplished by calculating the
Morning Warm-Up Optimal Start Time by averaging the
amount of time it takes to bring the RAT within 0.5°F
of the RAT heating setpoint for three consecutive days.
The three warm-up times are averaged and added to a
10-minute offset. The new time is used as the Morning
Warm-Up Optimal Start Time for the next day.
Adaptive Morning Warm-Up Setup
• Occupancy schedule MUST be programmed
for the Occ and Unocc start and stop times
through the SCHEDULE key.
• Occupancy schedule MUST be User Enabled.
• Morning warm-up MUST be User Enabled.
• Adapt morning warm-up MUST be User En-
abled.
• RAT heating setpoint MUST be set.
• Morning warm-up max time MUST be set.
• When the morning warm-up opt time exceeds
the morning warm-up max time, the morn-
ing warm-up opt time becomes the morning
warm-up max time.
• When the morning warm-up opt time is deter-
mined to be less than 15 minutes, the morning
warm-up opt time becomes 15 minutes.
• The default values for daily warm up time
[day 1], [day 2], [day 3] shall be initially set
to 60 minutes.
These values can be reset to the default val-
ues by turning morning warm-up to User Dis-
abled, then back to User Enabled.
Adaptive Morning Warm-Up Sequence of
Operation
It is recommended that all VAV or un-
deroor boxes are open to their maxi-
mum position during morning warm-up
operation.
• The Series 100 unit MUST be in an Unocc
mode before morning warm-up can be initi-
ated.
• The IPU board starts the morning warm-up
sequence.
• The supply fan starts. When configured
for VAV or Flexsys, the supply fan VFD is
controlled to the active duct static pressure
setpoint.
• When the RAT is greater than the RAT heat-
ing setpoint minus 1.0 °F, the IPU board does
not energize the heating sequence and it sets
the Daily Warm Up Time to 5 minutes.
• When the RAT is less than or equal to the
RAT heating setpoint minus 1.0 °F, the IPU
board energizes the heating sequence based
on the Morning Warm-Up Optimal Start
Time.
• Once the heating medium is started, the ac-
tive SAT setpoint is controlled as follows:
• VAV or Flexsys: To the heating SAT
setpoint
• SZVAV: To the 2nd stage heating
setpoint.
• The heating medium remains ON until
• The RAT is greater than or equal to the
RAT heating setpoint plus 0.5 °F
OR
• The morning warm-up command is re-
moved
OR
• The Series 100 unit enters an Occ mode

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals