SECTION 5 – SEQUENCE OF OPERATION
SMOKE PURGE
• The Series 100 units have three specialized smoke
purge sequences.
• These three sequences are outside the normal op-
erating sequences of the unit.
• They are typically only used in very specic ap-
plications, such as after a re or smoke event.
• Smoke purge sequences can be initiated either by
a hardwired input to CTB1 or through a command
from the BAS.
• When the unit enters a Smoke Purge mode, all cool-
ing and heating functions is immediately stopped.
Smoke Purge Setup
• Three different smoke purge sequences can be set:
1. Smoke Purge 1
2. Smoke Purge 2
3. Smoke Purge 3
• Each of these different sequences can be set for
one of three options:
1. Purge
2. Pressurization
3. Evacuation
• The different options for each sequence must be
selected in the PROGRAM-UNIT DATA menu.
Smoke Purge Sequence of Operation
Purge Mode
This mode is used to purge the space with fresh air:
1. Start the supply fan.
2. Start the return fan (if applicable).
3. Start the exhaust fan (if applicable).
4. Open outside air dampers to 100% (if applicable).
5. Close return air dampers to 0% (if applicable).
6. Open exhaust dampers to 100% (if applicable).
Pressurization Mode
This mode is used to pressurize the space in order to
force the air inside the space through the walls to adja-
cent spaces or outside the building envelope:
1. Start the supply fan.
2. Start the return fan (if applicable).
3. Stop the exhaust fan (if applicable).
4. Open outside air dampers to 100% (if applicable).
5. Close the return air dampers to 0% (if applicable).
Evacuation Mode
This mode is used to evacuate the space in order to
draw air through the walls from adjacent spaces or out-
side the building envelope:
1. Stop the supply fan.
2. Start the return fan (if applicable).
3. Start the exhaust fan (if applicable).
4. Close outside air dampers to 0% (if applicable).
5. Open return air dampers to 100% (if applicable).
6. Open the exhaust dampers to 100% (if applicable).

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals