EasyManuals Logo

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
JOHNSON CONTROLS
84
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 5 – SEQUENCE OF OPERATION
HGRH Faults
The HGRH Faults work to protect compressor
system 2 from damage as well as preventing un-
satisfactory temperature being delivered to the
space.
The HGRH system has three faults that can occur:
Lockout HGRH 1, 2, or 3.
Lockout HGRH 1
The IPU board monitors the temperature difference
before and after the HGRH coil whenever HGRH is
inactive. When the HGRH valve is stuck OPEN, a tem-
perature rise occurs when it should not.
HGRH is installed
HGRH status is inactive
Either compressor 2A or 2B is running
The current SAT is 8.0°F higher than the current
evaporator air temperature
Lockout HGRH 2
The IPU board monitors the temperature difference be-
fore and after the HGRH coil whenever HGRH is ac-
tive. When the HGRH valve is stuck CLOSED, there is
no temperature rise when there should be.
HGRH is installed
HGRH status is active
HGRH valve position is greater than 50%
The current SAT is 8.0°F less than the current
evaporator air temperature
Lockout HGRH 3
The IPU board monitors the discharge pressure for
compressor system 2. When a compressor starts from
system 2, HGRH goes active, and there is a rapid rise
in discharge pressure, then the HGRH 3-way stepper
valve is blocked and not allowing refrigerant to flow to
either the HGRH coil or the condenser coil.
HGRH is installed
Either compressor 2A or 2B is running
Compressor system 2 discharge pressure is greater
than 90% of the compressor system 2 unloading
pressure
CONDENSER FAN CONTROL
The Series 100 units have six condenser fans in-
stalled. There are two condenser fans for each
condenser section or “V.”
All six condenser fans have their own contactor.
The condenser fan A in each circuit starts when-
ever a compressor from that same circuit is started.
When condenser fan A has a condenser fan VFD
installed, the VFD is powered.
The condenser fan B in each circuit is controlled by
a pressure switch. The pressure switch is wired in
series with the condenser fan B contactor.
The pressure switch closes at 360 psig ± 10 psig
and opens at 240 psig ± 10 psig .
LD28122
FIGURE 43 - CONDENSER FAN CONTACTORS — FANS 1A AND 1B ONLY FOR COMPRESSOR SYSTEM #1

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals