SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
LD14363
FIGURE 54 - RETURN FAN ASSEMBLY
The return fan assembly always has a return fan
VFD.
A return fan assembly is ON whenever the supply
fan assembly is ON.
A return fan assembly has one VFD and two motor/
blower assemblies. See Figure 54 on page 103.
Exhaust fan assembly options are:
1. ON/OFF control based on outside air damper
position (SZVAV only)
2. ON/OFF control based on building pressure
3. Modulating damper with single speed ex-
haust fan
4. Modulating exhaust fan with barometric
damper
5. If the Series 100 unit was ordered as mod-
ulating damper - VFD, the exhaust fan can
also be controlled from the BAS.
Return fan assembly options are:
1. Return fan without exhaust
2. Return fan with exhaust
Exhaust Fan Assembly
The exhaust fan assembly in the Series 100 unit is
used to control building static pressure.
The exhaust fan assembly can be ordered as one
of four options.
The exhaust fan assembly only operates with a
demand from the building pressure setpoint or the
position of the outside air damper.
Exhaust Fan Assembly Setup
Power exhaust type must be set in the OPTIONS-
EXHAUST menu.
Building pressure setpoint must be set in the SET-
POINTS-EXHAUST menu.
Other setpoints specic to the power exhaust type
must be set in the SETPOINTS-EXHAUST menu.
ON/OFF Damper Control Sequence of
Operation
Power exhaust type must be set to ON-OFF
Damper Control in the OPTIONS-EXHAUST
menu.
Building pressure setpoint must be set in the SET-
POINTS-EXHAUST menu.
Economizer output for fan start must be set in the
SETPOINTS-EXHAUST menu.
Econo output for fan stop must be set in the SET-
POINTS-EXHAUST menu.
This control sequence uses a single speed exhaust
fan with a barometric damper.
When the position of the outside air damper is
greater than the economizer output for fan start,
the exhaust fan is turned ON.
When the position of the outside air damper is less
than the economizer output for fan stop, the ex-
haust fan is turned OFF.
ON/OFF Building Pressure Control Sequence
of Operation
Power exhaust type must be set to ON-OFF Pres-
sure Control in the OPTIONS-EXHAUST menu.
Building pressure setpoint must be set in the SET-
POINTS-EXHAUST menu.
Building pressure control offset must be set in the
SETPOINTS-EXHAUST menu.
This control sequence uses a single speed exhaust
fan with a barometric damper. When the current
building pressure is greater than the building pres-
sure setpoint plus the building pressure control
offset, the exhaust fan is turned ON.