SECTION 5 – SEQUENCE OF OPERATION
Supply Air Tempering
• This sequence uses the unit heating source to tem-
per the supply air during the winter months when
a large volume of outside air is required for ven-
tilation.
• It is only applicable on VAV and FlexSys cong-
ured units.
• SZVAV units utilize the comfort ventilation se-
quence. Refer to Comfort Ventilation on page
102 for a description of this sequence.
• Supply air tempering works best with either mod-
ulating gas or hot water/steam since the heat out-
put can be modulated down to a bare minimum.
Supply Air Tempering Setup
• The Series 100 unit must have a heating source
installed.
• The heating source must be User Enabled.
• Supply air tempering must be User Enabled in the
PROGRAM-COOLING menu.
Supply Air Tempering Sequence of Operation
• The supply air tempering sequence is slightly dif-
ferent depending on the heating source. The fol-
lowing sections detail the different sequences.
Modulating Gas and Hot Water/Steam Heat
• The IPU board monitors the current SAT.
• Supply air tempering becomes ACTIVE
when the current SAT (mixed SAT for Flex-
Sys) becomes 2.5°F colder than the active
cooling SAT setpoint (mixed SAT setpoint
for FlexSys) for 5 minutes.
• The heating source is turned ON when both
conditions below are satisfied:
• The economizer output is less than 5%
• There has been no compressor opera-
tion for 10 minutes
• The heating source is controlled to the active
cooling SAT setpoint (mixed SAT setpoint
for FlexSys).
• Supply air tempering becomes INACTIVE
when the following conditions are satisfied:
1. Modulating Gas Heat
• The current SAT (mixed SAT for
FlexSys) becomes 4.0°F warmer
than the active cooling SAT setpoint
(mixed SAT setpoint for FlexSys)
for 4 minutes.
• Modulating gas heat is at min low
fire
2. Hot Water/Steam Heat
• The current SAT (mixed SAT for
FlexSys) becomes 4.0°F warmer
than the active cooling SAT setpoint
(mixed SAT setpoint for FlexSys)
for 4 minutes.
• The hot water/steam valve position is
less than 2%
Staged Gas and Electric Heat
• The IPU board monitors the current SAT.
• Supply air tempering becomes ACTIVE
when both conditions below are satisfied:
1. The current SAT (mixed SAT for Flex-
Sys) becomes 2.5°F colder than the ac-
tive cooling SAT setpoint (mixed SAT
setpoint for FlexSys) for 5 minutes.
2. The current heat entering temperature is
less than the active cooling SAT setpoint
(mixed SAT setpoint for FlexSys) for 5
minutes.
• The heating source is turned ON when both
conditions below are satisfied:
1. The economizer output is less than 5%
2. There has been no compressor opera-
tion for 10 minutes
• The heating source is controlled to the active
cooling SAT setpoint (mixed SAT setpoint
for FlexSys).
• Supply air tempering becomes INACTIVE
when the current heat entering temperature
becomes greater than the active cooling SAT
setpoint for 5 minutes.

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals