EasyManua.ls Logo

Johnson Controls 100 Series - FIGURE 38 - HGRH 3-Way Stepper Valve; TABLE 30 - HGRH Control Board Green LED Flash Descriptions

Johnson Controls 100 Series
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
80
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 5 – SEQUENCE OF OPERATION
The HGRH system uses a 3-way stepper motor
to control the ow of discharge gas between the
condenser coil and the HGRH coil
The HGRH system has a bled solenoid valve in-
stalled to allow oil drainage back into the com-
pressor
HGRH 3-Way Stepper Valve
The HGRH system uses a 3-way stepper valve to
control the refrigerant ow between the condens-
er coil and the HGRH coil
The 3-way stepper valve is a Sporlan
®
MTW-17
The valve is controlled by a Sporlan IB-G inter-
face board
The 3-way valve has a minimum and maximum
position whenever HGRH is active. These values
cannot be changed.
Minimum: 25%
Maximum: 95%
See Figure 38 for 3-way stepper valve outputs/
inputs
Outlet A is piped to the condenser coil
Outlet B is piped to the HGRH coil
Outlet C is piped from the discharge line
CKT 2
OUTLET B: TO HGRH COIL
OUTLET A: TO CONDENSER
COIL
FROM DISCHARGE
LINE CKT 2
B
A
LD20876
FIGURE 38 - HGRH 3-WAY STEPPER VALVE
HGRH Control Board
The HGRH control board is factory installed and
programmed. No eld setup is required.
The HGRH control board is powered by 24 VAC
The HGRH control board receives a 0–10 VDC
signal from the IPU board. The HGRH control
board then sends pulse signals to the 3-way step-
per valve to modulate open/closed.
TB9-11 and TB9-12 sends a 0–10 VDC signal
The HGRH control board has three LEDs
Red LED: This status LED is lit whenever
there is 24 VAC present
Yellow LED: This closed LED is only lit
when the 3-way valve is fully closed
Green LED: This valve open LED flashes in
different sequences depending on the valve
position
TABLE 30 - HGRH CONTROL BOARD GREEN LED
FLASH DESCRIPTIONS
NUMBER OF FLASHES VALVE POSITION % OPEN
1 Flash 0–10%
2 Flashes 10–20%
3 Flashes 20–30%
4 Flashes 30–40%
5 Flashes 40–50%
6 Flashes 50–60%
7 Flashes 60–70%
8 Flashes 70–80%
9 Flashes 80–90%
10 Flashes 90–99%
Remains Lit 100%

Table of Contents

Other manuals for Johnson Controls 100 Series

Related product manuals