EasyManua.ls Logo

Johnson Controls 100 Series - Low Ambient Inhibit; Low Ambient Operation; High Discharge Pressure Unloading; Hot Gas Reheat (HGRH)

Johnson Controls 100 Series
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
79
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
When both compressors are operating at the time of
the trip, the one with the longest run time shuts OFF.
After 1 minute, the IPU board looks again at the
suction line temperature. When the temperature is
still below the suction temperature low limit, the
compressor still operating shuts down.
Both compressors remain OFF until the suction
line temperature rises over the suction tempera-
ture low limit by 10.0°F for 10 minutes.
High Discharge Pressure Unloading
This sequence helps prevent compressor safety
trips and lockouts on a compressor system due to
higher than normal ambient temps or dirty con-
denser coils.
For this sequence to operate both of the below
conditions must be met:
a. A discharge pressure transducer must be in-
stalled and reading properly for a compressor
system.
b. Both compressors in a compressor system
must be operating.
The IPU board monitors the discharge pressure in
a given compressor system.
When the discharge pressure reaches the system
unloading pressure, one of the compressors is shut
down. Compressor status displays High DP Unload.
The system unloading pressure can be found under
the SETPOINTS-COMPRESSOR SYSTEM menu.
When High DP Unload is displayed, the IPU board
records the current OAT.
Once the current OAT is 5.0°F less than the OAT at
the time High DP Unload started, the compressor
system is returned to normal operation.
Low Ambient Inhibit
The IPU board displays this compressor status
message when the current OAT is below the me-
chanical cooling lockout temperature.
The mechanical cooling lockout temperature is a
xed value of 50.0°F when a compressor system
has no low ambient package installed or the dis-
charge pressure transducer reading is out of range.
The mechanical cooling lockout temperature is
user adjustable on a compressor system with a low
ambient package installed.
For compressor systems with a low ambient package
installed, mechanical cooling lockout temperature
can be found under SETPOINTS-COOLING menu.
Low Ambient Operation
Mechanical cooling is not permitted below 50.0°F
OAT unless a compressor system has an optional
low ambient package installed.
The low ambient package can be installed on com-
pressor system 1, compressor systems 1 and 2, or all
three compressor systems.
The low ambient package consists of a discharge
pressure transducer and condenser fan VFD.
The condenser fan VFD is controlled directly by
the discharge pressure and is not controlled by the
IPU board.
The condenser fan VFD is always installed on the
rst condenser fan for a compressor system.
The condenser fan VFD operation is described in
further detail in the Low Ambient Kit section on
page 85.
HOT GAS REHEAT (HGRH)
The Series 100 units can have an optional HGRH
system.
HGRH is only available on VAV and SZVAV con-
gured units
HGRH is factory installed when the unit is built.
There are no eld installation kits for HGRH.
The HGRH system allows a standard DX cooling
unit to provide dehumidication of the supply air.
HGRH System
The HGRH system adds sensible heat to the air
being delivered to the space. This allows the DX
cooling coil to operate at a lower temperature and
remove excess moisture from the air without neg-
atively affecting personal comfort
When a HGRH system is installed, the unit has a
HGRH coil installed after/downstream of the DX
cooling coil
The HGRH system uses the discharge gas from
compressor circuit 2
When HGRH is active, the number of available
cooling stages is reduced

Table of Contents

Other manuals for Johnson Controls 100 Series

Related product manuals