EasyManuals Logo
Home>Johnson Controls>Air Conditioner>100 Series

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
JOHNSON CONTROLS
91
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
• The modulating gas valve is at maximum
position at approximately 8–9 VDC from the
IPU board.
• When more heat is needed, the IPU board
brings on the next stage depending on the gas
heat capacity.
a. 375 MBH
• On a 375 MBH unit, there is only one
furnace section split into two halves: 1A
and 1B.
• Once furnace 1A has reached high fire
max position, furnace 1B is ignited.
• Furnace 1A stays on high fire but the
modulating valve is modulated between
minimum (4–4.5 VDC) and maximum
(8–9 VDC) positions.
b. 750 MBH
• On a 750 MBH unit, there are two fur-
nace sections.
• Furnace 1 is one section split into two
halves: 1A and 1B.
• Once furnace 1A has reached high fire
max position, furnace 2 is started on low
fire.
• Furnace 1A starts at low fire min and
goes through the low fire to high fire se-
quence as described above.
• When more heat is still needed, furnace
2 switches to high fire and furnace 1A
starts at low fire min and goes through
the low fire to high fire sequence as de-
scribed above.
• When more heat is needed and furnace
2 is on high fire and furnace 1A is at
high fire max, the IPU brings on furnace
1B and furnace 1A follows the sequence
listed under 375 MBH.
c. 1125 MBH
• On a 1125 MBH unit, there are three
furnace sections.
• Furnaces 1 and 2 are described as above.
• Furnace 3 is an exact match of furnace 2.
• Once Furnace 2 is at high fire,and fur-
nace 1A is at high fire max, furnace 3 is
started on low fire.
• The same sequence is followed on fur-
nace 3 and furnace 1A and 1B as listed
above in the 750 MBH sequence.
• Furnace 2 remains at high fire during
the furnace 3 sequence as long as the
heating demand keeps increasing.
LD10151
FIGURE 48 - MODULATING GAS HEAT STAGING SEQUENCE

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals