JOHNSON CONTROLS
117
SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
6
TABLE 43 - COOLING
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
SUPPLY AIR TEMP
CURRENT -20.0°F To 180.0°F Look Up Table
Unit Type Equals Constant
Volume Or Variable Air Volum
ACTIVE SP 50.0°F To 150.0°F Derived
FLEX EVAP TEMP
CURRENT -20.0°F To 180.0°F Look Up Table Unit Type Equals FLEXSYS
And Current Oper Mode Is
OCC Cooling w/ byp
ACTIVE SP 50.0°F To 60.0°F Derived
MX SUPPLY AIR TEMP
CURRENT -20.0°F To 180.0°F Look Up Table
Unit Type Equals FLEXSYS
SETPOINT 1 50.0°F To 75.0°F 65.0°F
Setpoints/
Cooling
COOLING CONTROL
OFFSET
1.0°F To 100.0°F Derived
RETURN AIR DIFF SP 2 2.0°F To 10.0°F 6.0°F
Setpoints/
Cooling
Unit Type Equals FLEXSYS
ZONE TEMP*
CURRENT -20.0°F To 180.0°F Look Up Table
Unit Type Equals Constant
Volume Or Variable Air Volum
OCC ZONE COOLING
SETPOINT
1
OCC Zone Heating
+ 2.0°F To 85.0°F
72.0°F
Setpoints/
Cooling
ZONE TEMP*
CURRENT -20.0°F To 180.0°F Look Up Table
Unit Type Equals Constant
Volume Or Variable Air Volum
UNOCC ZONE COOLING
SETPOINT
1
UNOCC Zone
Heating + 2.0°F To
95.0°F
85.0°F
Setpoints/
Cooling
RETURN AIR TEMP
CURRENT -20.0°F To 180.0°F Look Up Table
Unit Type Equals Variable Air
Volum Or FLEXSYS
RAT COOLING
SETPOINT
1
RAT Heating Setp
+2.0°F To RAT For
High Sat
70.0°F
Setpoints/
Cooling
RETURN AIR BYPASS
CURRENT 0–100% Derived
Unit type equals FLEXSYS
ACTIVE SP 0–100% Derived
BYPASS DAMPER
POSITION
0–100% Derived Unit type equals FLEXSYS
UNDERFLOOR AIR
TEMP -20.0°F To 180.0°F Look Up Table
Unit type equals FLEXSYS and
dewpoint reset equals enabled
HUMIDITY 0–100% Derived
UNDERFLOOR SLAB
TEMP -20.0°F To 180.0°F Look Up Table
Unit type equals FLEXSYS and
dewpoint reset equals enabled
DEW POINT 30.0°F To 100.0°F Derived
MAXIMUM BYPASS 1 20–40% 40%
Setpoints/
Cooling
Unit type equals FLEXSYS
DEW POINT RESET 1
User Enabled User
Disabled
User Disabled
Program/
Cooling
Unit type equals FLEXSYS
UNDER FLR TEMP
OVRD
1 Active - Inactive Derived Unit type equals FLEXSYS

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals