JOHNSON CONTROLS
64
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 5 – SEQUENCE OF OPERATION
Continuous Ventilation
• User adjustable program that allows the supply
fan to run continuously when in Occ mode.
• It can be found under PROGRAM-VENTILA-
TION menu.
• When continuous ventilation is User Enabled, the
supply fan is ON whenever the unit is in an Occ
mode.
• When continuous ventilation is User Disabled, the
supply fan is started with a demand for cooling or
heating. The APS must be closed before cooling or
heating operation is permitted.
Supply Fan Modulation
• When the Series 100 unit is in Occ Standby
(continuous ventilation is User Enabled) or Occ/
Unocc Cooling Low, the supply fan is running at
the SZVAV minimum speed.
• If the current zone temperature rises 1.5°F above
the active zone temperature setpoint, the IPU
board starts to increase the supply fan speed.
• The supply fan speed keeps increasing as the zone
temperature rises higher above the active zone
temperature setpoint.
• When the zone temperature is above the active
zone temperature setpoint by 2.5°F, the supply fan
is at full speed (100%).
Cooling And Heating Operation
• On a SZVAV unit, cooling and heating demands is
determined in one of two ways:
1. Zone temperature
a. Wired zone temperature
b. Communicated zone temperature
2. Staged input
a. Thermostat (2 stage cooling/heating)
b. BAS commands
• The zone control method must be selected under
the PROGRAM-UNIT DATA menu:
1. Wired Zone Temperature: Hardwired sensor
to CTB1, 10K Type III thermistor
2. Comm Zone Temperature: Zone temperature
signal from a BAS (BACnet MS/TP point
AV40 ZONE_TEMP_BAS)
3. Staged: Either a thermostat is connected to the
appropriate terminals on CTB1 or BAS com-
mands are used for Y1, Y2, W1, W2, and G
terminals
• The occ/unocc cooling setpoints can be viewed un-
der the SETPOINTS-COOLING menu.
• The "OCC/UNOCC HEATING" SPs can be viewed
under the SETPOINTS-HEATING menu.
• These setpoints are also available on a BAS.
• Table 22 on page 65 shows the relationship be-
tween zone temperature and unit modes.
SZVAV Supply Air Temperature (SAT)
• Once a SZVAV congured unit enters an Active
Cooling or Heating mode, the IPU board utilizes
as many stages of cooling or heating as needed to
achieve and maintain the "ACTIVE SAT" setpoint.
• This includes economizer operation if outside air
conditions are suitable.
• "1ST AND 2ND STAGE COOLING" SPs can be
found under the SETPOINTS-COOLING menu.
• "1ST AND 2ND STAGE HEATING" SPs can be
found under the SETPOINTS-HEATING menu.
• These SPs are also available on a BAS.
• Table 23 on page 66 shows the active S AT set-
points for each unit mode in SZVAV.

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals