JOHNSON CONTROLS
178
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 8 – SERVICE
TABLE 67 - FAULTS LOCKOUT
HISTORY SCREEN
WORDING
DESCRIPTION RESET
SHOW WHEN
UNIT TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
LOCKOUT-
COMPRESSOR
SYSTEM * TIME
OUT
See below
System
Lockout
Comp System *
- Safety Lockout
Cooling
Heating
Fault
LOCKOUT -
COMPRESSOR
SYSTEM *
High press SW, comp motor protector,
or overcurrent protector open - 3 times
in 120 minutes on comp system *
System
Lockout
Comp System *
- Safety Lockout
Cooling
Heating
Fault
LOCKOUT-HIGH
DUCT PRESSURE
Duct static press current .+ Duct static
over pressure
Unit
Lockout
Unit Type Is VAV
Or FlexSys
Supply Sys
Status Safety
Lockout
Fan Fault
LOCKOUT - HOT
WATER FREEZE
The hydronic freeze stat switch
remained closed >= 5 minutes
Unit
Lockout
Heat Type Hot
Water / Steam
Heating Sys
Status - Safety
Lockout
Cooling
Heating
Fault
LOCKOUT-LPCO
Low pressure cutout open - 3 times in
120 minutes on compr system *
System
Lockout
Comp System *
- Safety Lockout
Cooling
Heating
Fault
LOCKOUT -
MANUAL STOP *
The compressor system has been
placed in the stop mode either
through the user interface or by a
communicated input
System
Lockout
Comp Sys *
Status Disabled
LOCKOUT -
MANUAL UNIT
STOP
The unit is shut down through the
shut down switch on the unit or by an
external hardwired or communicated
input
Unit
Lockout
Unit - Overall
Status Local
Stop
LOCKOUT - OAT
SENSOR
Outside air temp sensor is out of
range for >= 10 seconds
Unit
Lockout
Comp Sys *
Status Safety
Lockout; Econo
Sys Status
Safety Lockout
Sensor/
Misc
Fault
LOCKOUT -
RETURN FAN
Return fan status is low and time from
start >= 30 sec unit lockout
Unit
Lockout
Power Exhaust
Type Is Return
Fan W/Exh Or
Return Fan W/O
Exh And The
Supply Fan Is On
Unit - Overall
Status Unit
Lockout
Fan Fault
LOCKOUT - SAT
SENSOR
Supply air temp current sensor is out
of range for >= 10 seconds
Unit
Lockout
Unit Type Is
Constant Volume
Or Variable Air
Volume
Sensor/
Misc
Fault
LOCKOUT-
SUPPLY FAN
Supply fan status is low and time from
start > = 30 sec unit lockout
Unit
Lockout
Unit - Overall
Status Unit
Lockout
Fan Fault
* Can be 1, 2, or 3
“WRN - COMP SYSTEM * INHIBIT” - This WARNING indicates the compressor system safety circuit experienced a trip but reset prior to the
exploration of the 60 minute reset time function. If the safety circuit does not reset in 60 minutes it is replaced with a “LOCKOUT - COMPRES-
SOR SYSTEM * TIME OUT” message.
“AUTO RESET - COMPRESSOR SYSTEM * CLEAR” - Whenever there is a compressor safety trip the Primary IPU board initiates the
“COMPR STATUS CLEAR TIME *” timer. The Primary IPU board records the time it takes for the trip to clear. When the fault clears “COM-
PRESSOR SYSTEM * CLEAR” shows the time it took for the fault to clear in the HISTORY buffer.
“LOCKOUT-COMPRESSOR SYSTEM * TIME OUT” – If the “COMPR STATUS CLEAR TIME *” timer reaches 60 minutes a “LOCKOUT -
COMPRESSOR SYSTEM * TIME OUT” is indicated in the HISTORY buffer.