EasyManua.ls Logo

Johnson Controls 100 Series - FIGURE 46 - Modulating Gas Furnace Sections

Johnson Controls 100 Series
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
89
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
LD28125
FIGURE 46 - MODULATING GAS FURNACE SECTIONS
Modulating Gas Heat Sequence of Operation
Once the IPU board determines there is a demand
for heat, a 24 VAC signal is sent to furnace 1A.
At the same time, the IPU board sends a 24 VAC
signal to the 6R (1A high re relay).
The inducer motor for furnace 1A starts on high
speed and make both the low and high pressure
switches.
Once the pressure switches close, 24 VAC runs
through two limit switches and back into the igni-
tion control. This lets the ignition control know
that all safety switches are closed.
There is a 30 Second Purge Timer that allows the
inducer motor to ush the furnace with clean air.
After the 30 Second Purge Timer expires, the igni-
tion control:
1. Sends 24 VAC to the low and high fire so-
lenoid of the gas valve and produces a high
voltage spark for 7 seconds.
2. Modulates the modulating gas valve to mini-
mum high fire.
Furnace 1A gas burners ignite.
The ignition control monitors the ame signal for
15 seconds.
After 15 seconds of steady ame rectication, the
ignition control:

Table of Contents

Other manuals for Johnson Controls 100 Series

Related product manuals